EM500 Open-Loop Vector Control Inverter User Manual
342
outages and parking choice
0: Power outages saved
1: Power outages Unsaved
F27.03 Ones Place set to 0:
Auto-reset: The feedforward gain is automatically reset when it is stopped
F27.03 Ones Place set to 1:
Terminal reset: The feedforward gain is reset via the terminal
F27.03Tens Place set to 0:
Power-outage saved: Feed-forward gain after Power-outage, power-on can be restored to
the value before Power-outage
F27.03 Tens Place set to 1:
Power-outage is not saved: feedforward gain Power-outage, power-up again when the
feed-forward gain goes back to the initial gain
No.
Function
Range
Unit
Default
Type
F27.04
Upper Limit
feedforward gain
0.00~500.00
%
500.00
The feedforward gain upper limit value or the upper limit value of the change
No.
Function
Range
Unit
Default
Type
F27.05
Feedforward
initial gain
0.00~500.00
%
50.00
The starting value of the feedforward gain
No.
Function
Range
Unit
Default
Type
F27.06
feedforward gain
filtering time
0~1000
ms
0
Filtering of the feedforward gain, it is generally not required setting.
No.
Function
Range
Unit
Default
Type
F27.07
Feedforward range
0
0.00~ Feedforward range1
%
4.00
F27.08
Feedforward range
1
Feedforward range 1~
Feedforward range 2
%
12.00
F27.09
Feedforward range
2
Feedforward range 2~
Feedforward range 3
%
23.00
F27.10
Feedforward range
3
Feedforward range 3~
Feedforward range 4
%
37.00
F27.11
Feedforward range
Feedforward range 4~
%
52.00