EM500 Open-Loop Vector Control Inverter User Manual
154
7. Parameter Description
7.1 F00 Group: General Parameter
No.
Function
Range
Unit
Default
Type
F00.01
Control Mode
of Motor 1
0: V/F control (VVF)
1: Sensorless Vector Control
(SVC)
0
F00.01=0: V/F control (VVF)
Inverter is applicable for the occasions when multiple motors are driven by a single
inverter or it is not required for quick response or high precision.
F00.01=1: Sensorless Vector Control (SVC)
Open loop vector control mode is usually applied to high-performance control occasions
and one inverter can drive one motor only. The loads include machine tool, centrifuge,
wire-drawing machine and injection moulding machine.
1. Before running in the vector control mode, inverter needs to autotune motor
parameters to obtain correct motor parameters and enhance the control
performance.
2. While using the vector control mode, inverter can only have one
motor. Motor and inverter shall not be much different from each other in
capacity, otherwise the control performance may decrease or the system cannot
work normally.
No.
Function
Range
Unit
Default
Type
F00.02
Command
Source
0: Keypad Control
(LOC/REM indicator on)
1: Terminal Control
(LOC/REM indicator off)
2: Communication Control
(LOC/REM indicator flickers)
0