EM500 Open-Loop Vector Control Inverter User Manual
329
The above parameters are used to timing multiple preset pressure water supply time and
set the corresponding pressure.
Pressure is set to 0, then system is in standby state at the corresponding time.
Set the time period, follow the principle of T1 ≤ T2 ≤ T3 ≤ T4 ≤ T5 ≤ T6. It is
recommended to start from T6.
Before T1 time, the pressure is the one in T6 period.
If the start time of a time period is the same as the start time of the previous period, the
two sections are combined and the pressure of the latter period is used.
Unconventional
Time timing
choice of water
supply
0: Saturday And Sunday
effective
1: Effective on Sunday, Saturday
is invalid
2: Saturday and Sunday is invalid
F26.17=0: Saturday And Sunday effective
Saturday and Sunday timing given by the unconventional date
F26.18=1: Effective on Sunday, Saturday is invalid
Sunday timing is given by the unconventional date, Saturday timing given by the
conventional date