Attentions:
★ At preset speed running, inverter start/stop is determined by the function code
F00.02.
★
At preset speed running mode, inverter acceleration/deceleration time can be
controlled by the external terminal set as the acceleration/deceleration time.
Direction at preset speed running is controlled by terminals F/R and RUN.
0: Stop after Single Running
1: Stop after Limited Times of Cycles
2. Run at Last Preset Speed after
Limited Times of Cycles
3: Continuous Cycle
In addition to preset speed function, there is simple PLC function, which provides
four control modes. See Table 7-11 for details.
Table 7-11 PLC Running Mode
Inverter stops after running at the last preset speed.
Run circularly; the cycle times is set through F08.16; inverter stops
after the cycles are complete.
Run circularly; the number of cycle times is set through F08.16; after
having completed the running at the last preset speed, inverter keeps
running at the last preset speed until a stop command is received.
Run continuously and circularly until a stop command is received.
★
Inverter starts the judgment from the running time of the 15
th
preset speed (F08.48) to
the first preset speed. A function code not set as 0 is the last preset speed.