EM500 Open-Loop Vector Control Inverter User Manual
209
after the set time is out. If F04.04=0.00, DC brake is disabled at start.
★ The process of starting DC brake is shown in Figure 7-18.
This function may be enabled when the single inverter serves multiple
motors and inverter is starting
50.0 - 500.0 (100.0=Idling
Current)
Inverter develops a magnetic field as the set pre-excitation current, and starts
running after the set pre-excitation time (F04.07) is out. If the set pre-excitation is 0,
inverter will start directly without the pre-excitation link.
F04.06 pre-excitation current is a percentage relative to motor’s rated no load
current.
Rotation Speed
Tracking Method
0: Start from Maximum
Frequency
1: Start from Stop
Frequency
2: Start from Power
frequency
When the starting mode is selected as the torque tracking start (F04.00=1), inverter
will perform the torque tracking as per the setting through F04.08 at start. Please select a
proper mode according to the working condition, so as to better track present motor
This mode can be selected when inverter starts tracking downwards from the
maximum frequency (F04.08=0) and the running status of motor is completely unsure
(motor is in rotation status when inverter is powered on).
;
If F04.08=1, it means that inverter starts tracking from the stop frequency. Generally,
If F04.08=2, it means that inverter starts tracking from the power frequency. This
mode can be selected if the power frequency changes to the frequency conversion.