EM500 Open-Loop Vector Control Inverter User Manual
281
No.
Function
Range
Unit
Default
Type
F13.06
Torque Control
Acceleration/Decelerat
ion Time
0.00 - 120.00
s
0.05
Setting F13.06 can make the motor speed change smoothly
The value set by F13.06 refers to the time that the torque current increases from 0 to
the rated torque current or decreases from the rated current to 0.
No.
Function
Range
Unit
Default
Type
F13.08
Upper Limit
Frequency of Torque
Control
0: Set through F13.09
1: AI1
2: AI2
3: AI3
4: AI4 (Expansion Card)
5: High-Frequency Pulse Input
(X7)
6: Communication Percentage
Setting
7: Direct Communication
Setting
0
F13.09
Upper Limit
Frequency of Torque
Control
0.00 - Maximum Frequency
F00.16
Hz
50.00
F13.10
Upper Limit
Frequency Offset
0.00 - Maximum Frequency
F00.16
Hz
0.00
F13.18
Reverse speed
limit
0100
%
100
F13.19
Reverse torque
limit
01
1
F13.08=0: Set through F13.09
Under torque control mode, the upper limit frequency is set through F13.09.
F13.08=1: AI1
F13.08=2: AI2
F13.08=3: AI3
F13.08=4: AI4 (Expansion Card)
Under the torque control mode, the upper limit frequency is set through AI