Attribute Value
Sub-index 0x03
LCP Parameter number 12-02
Name IP mask
Data type UNSIGNED32
Access Read only
PDO mapping Yes
Value range 0x0000 0000–0xFFFF FFFF
Default value 0
Sub-index 0x04
LCP Parameter number 12-03
Name IP gateway
Data type UNSIGNED32
Access Read only
PDO mapping Yes
Value range 0x0000 0000–0xFFFF FFFF
Default value –
Sub-index 0x08
LCP Parameter number 12-04
Name Mac address
Data type OCTET_STRING
Access Read only
PDO mapping Yes
Value range –
Default value –
Table 7.251 0x400A: Communication Settings
7.22.7 Parameters 15-01 and 15-02: Total Running Time (0x5807)
The servo drive has 2 counters for the running time.
The 1
st
object is a non-resettable counter (32 bits). It contains the time in seconds that the servo drive has been running
(enabled). This means that the counter is running as long as the servo drive is in state Switched on, Operation enabled, or
Quick stop active.
The 2
nd
object contains the time in seconds that the servo drive has been running (enabled). This means that the counter is
running as long as the servo drive is in state Switched on, Operation enabled, or Quick stop active.
This 2
nd
counter is resettable by writing 0 to it, so it can be used to track service intervals.
Attribute Value
Index 0x5807
Name Total running time
Object code Array
Data type UNSIGNED32
Sub-index 0x00
Description Value of highest sub-index
Access Read only
PDO mapping No
Default value 0x02
Sub-index 0x01
LCP Parameter number 15-01
Description Total running time drive
Servo Drive Parameter Descr...
VLT
®
Integrated Servo Drive ISD
®
510 System
350 Danfoss A/S © 01/2017 All rights reserved. MG36D102