EasyManua.ls Logo

Danfoss VLT series

Danfoss VLT series
390 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
ms Manufacturer-specic
r Reserved
oms Operation mode specic
h Halt
fr Fault reset
eo Enable operation
qs Quick stop
ev Enable voltage
so Switch on
cs Control set selection
do Set/reset the digital output
dcs Digital CAM switching functionality enabled/disabled
Table 7.3 Denition of Controlword Bits
Bit Value Denition
11 0 Digital CAM switching functionality must be disabled (see chapter 2.5.1 Digital CAM Switch).
1 Digital CAM switching functionality must be enabled (see chapter 2.5.1 Digital CAM Switch).
12 0 Digital output is cleared.
1 Digital output is set.
15 0 Control parameter set 1 is used (objects 0x2012 and 0x2013; see chapter 2.3.6 Control Loops).
1 Control parameter set 2 is used (objects 0x2014 and 0x2015; see chapter 2.3.6 Control Loops).
Table 7.4 Manufacturer-specic Bits in Controlword
Command
Controlword bits
Transitions
Bit 7 Bit 3 Bit 2 Bit 1 Bit 0
Shutdown 0
X
1)
1 1 0 2, 6, 8
Switch on 0 0 1 1 1 3
Switch on and enable operation 0 1 1 1 1
3, 4
2)
Disable voltage 0
X
1)
X
1)
0
X
1)
7, 9, 10, 12
Quick stop 0
X
1)
0 1
X
1)
7, 10, 11
Disable operation 0 0 1 1 1 5
Enable operation 0 1 1 1 1 4, 16
Fault reset
01
X
1)
X
1)
X
1)
X
1)
15
Table 7.5 Command Coding
1) X denotes Don’t care.
2) Automatic transition to Enable operation state after executing Switched on state functionality.
NOTICE
See chapter 2.3.1 State Machine for the relevant transitions.
7.2.1.1 Controlword in Prole Position Mode
Table 7.6 shows the structure of the Controlword. Table 7.7 denes the values for bit 4, 5 and 9 of the Controlword. Table 7.8
denes the values for bit 6 and 8 of the Controlword. If no positioning is in progress, the rising edge of bit 4 starts the
positioning of the axis. If positioning is in progress, the values given in Table 7.7 dene the behavior.
15
10 9 8 7 6 5 4 3 0
See Table 7.2
Change on
setpoint
Halt See Table 7.2 Abs/rel
Change set
immediately
New
setpoint
See
Table 7.2
MSB LSB
Table 7.6 Controlword for Prole Position Mode
Servo Drive Parameter Descr... Programming Guide
MG36D102 Danfoss A/S © 01/2017 All rights reserved. 233
7 7

Table of Contents

Other manuals for Danfoss VLT series

Related product manuals