Attribute Value
Sub-index 0x03
LCP Parameter number 12-02
Name IP mask
Data type UNSIGNED32
Access Read only
PDO mapping Yes
Value range 0x0000 0000–0xFFFF FFFF
Default value 0
Sub-index 0x04
LCP Parameter number 12-03
Name IP gateway
Data type UNSIGNED32
Access Read only
PDO mapping Yes
Value range 0x0000 0000–0xFFFF FFFF
Default value –
Sub-index 0x08
LCP Parameter number 12-04
Name Mac address
Data type OCTET_STRING
Access Read only
PDO mapping Yes
Value range –
Default value –
Sub-index 0x0D
LCP Parameter number –
Name Network topology
Data type UNSIGNED8
Access Read/write
PDO mapping No
Value range 0, 1
Default value 0
Table 8.24 0x400A: Communication Settings
8.30
Object 0x5020: Control Source
This object shows the control source for the SAB.
•
Value 0: Fieldbus is in control (writes are only
accepted from the eldbus).
•
Value 1: The LCP is in control (writes are only
accepted from the LCP).
Attribute Value
Index 0x5020
Description Control source
Object code Var
Data type UNSIGNED16
Sub-index 0x00
LCP parameter number –
Access Read/write
Attribute Value
PDO mapping Yes
Value range 0 or 1
Default value 0
Table 8.25 Object 0x5020: Control Source
8.31 Object 0x5807: Total Running Time
The SAB has 2 counters for the running time:
•
Non-resettable counter (32 bits)
- Counts the time that the SAB has been
running in state Normal operation in
seconds.
•
Resettable counter
- Counts the time that the SAB has been
running in state Normal operation in
seconds.
- Can be reset by writing 0 to it and can
therefore be used to track service
intervals.
Attribute Value
Index 0x5807
Description Total running time
Object code Array
Sub-index 0x00
LCP parameter number –
Description Number of entries
Access Read only
PDO mapping No
Value range 0x02
Default value 0x02
Sub-index 0x01
LCP parameter number 15-01
Description Total running time SAB
Access Read only
PDO mapping Yes
Object code Var
Data type UNSIGNED32
Sub-index 0x02
LCP parameter number 15-02
Description Total running time user
Access Read/write
PDO mapping Yes
Object code Var
Data type UNSIGNED32
Table 8.26 Object 0x5807: Total Running Time
SAB Parameter Description Programming Guide
MG36D102 Danfoss A/S © 01/2017 All rights reserved. 365
8 8