16 - 23
16.2 Troubleshooting
16.2.13 When operation is not normal due to script file execution
16
TROUBLESHOOTING
Figure 16.12 Disabling script file execution (for the Q12DCCPU-V and Q06CCPU-V) (continued)
Yes
No
Has the script file
execution stopped?
Consult your local Mitsubishi service
center or representative, explaining the
details of the problem.
End
1
Remove the CompactFlash card from
the C Controller module.
Activate the default IP setting mode of
the hardware self-diagnostic function,
and restart the C Controller module.
The C Controller module is placed in
the following status.
The IP address returns to the default
IP address.
Script files in the standard RAM or
standard ROM are deleted.
( Page 15-105, Section 5.)
Correct either of the following.
Script file in the standard RAM or
standard ROM
User program started from a script file
in the standard RAM or standard ROM
Page 6-72, Section 6.10