16
TROUBLESHOOTING
16.2 Troubleshooting
16.2.13 When operation is not normal due to script file execution
16 - 24
9
DEVICE DESCRIPTION
10
MULTIPLE CPU SYSTEM
OVERVIEW
11
MULTIPLE CPU SYSTEM
CONFIGURATION
12
CONCEPT OF MULTIPLE
CPU SYSTEM
13
COMMUNICATIONS
BETWEEN CPU
MODULES
14
PARAMETERS ADDED
FOR MULTIPLE CPU
SYSTEMS
15
STARTING A MULTIPLE
CPU SYSTEM
16
TROUBLESHOOTING
(2) For the Q06CCPU-V-B
* 1 For restrictions on the functions, refer to the following.
C Controller Module User's Manual (Utility Operation, Programming)
Figure 16.13 Disabling script file execution (for the Q06CCPU-V-B)
Yes
No
Error occurred
When the user program was started
from a script file in the standard ROM,
perform the following.
Activate the default IP setting mode of
the hardware self-diagnostic function,
and restart the C Controller module.
The C Controller module is placed in
the following status.
The IP address returns to the default
IP address.
Script files in the standard ROM are
deleted.
( )
Has the script file
execution stopped?
Consult your local Mitsubishi service
center or representative, explaining the
details of the problem.
Correct the script file in the standard
ROM, or correct the user program
started from the script file in the standard
ROM.
End
Yes
End
No
Compile the user program and
regenerate an execution file according
to the C Controller module
specifications.
Does the endian
format of the execution file match
the specification of the
C Controller module?
*1
Page 6-72, Section 6.10