APPENDICES
Appendix 9 Connection with GX Works2/GX Developer
Appendix 9.2 Accessing other stations
APPX - 35
A
I
4) When "Other station (Single network)" is specified for "Other station", specify
accessed network type
*1
for "Network route".
When "Other station (Co-existence network)" is specified for "Other station",
for "Network route" specify the accessed network type
*1
to which the C
Controller module is connected.
* 1 "C24" and "Ethernet" cannot be specified for the network type.
After specifying the network type, set "Network No.", "Station No." and "Head
I/O No." Setting items vary depending on the network type.
5) Only when "Other station (coexistence network)" is specified for "Other
station", specify the accessed network type for "Co-existence network route".
After specifying the network type, set "Network No.", "Station No." and "Head
I/O No." Setting items vary depending on the network type.
6) If the CPU to be accessed is a multiple CPU system, set the accessed CPU for
"Multiple CPU setting".
For more details, refer to the following.
GX Works2 Version1 Operating Manual (Common)
(2) GX Developer
1) [Online] Select [Transfer setup].
2) Set "PC side I/F" and "PLC side I/F" in the same way as for accessing another
CPU in a multiple CPU system. ( Page App-25, Appendix 9.1)
3) If connection via a system consisting of single type of network and multi-layer
systems is used, set "Other station setting" to "Other station (Single network)".
If connection via two different types of networks is used, set "Other station" to
"Other station (Co-existence network)".