EasyManua.ls Logo

Rohde & Schwarz R&S FSL3 - Page 911

Rohde & Schwarz R&S FSL3
1734 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INPut Subsystem R&S FSL
1300.2519.12 6.152 E-11
C
haracteristics
*RST value: 50
S
CPI: conform
Mode
All
INPut<1|2>:UPORt[:VALue]?
This command queries the control lines of the user ports.
This command is a query and therefore has no *RST value.
Example
INP:UPOR?
Characteristics
RST value:
SCPI: device–specific
Mode
all
INPut<1|2>:UPORt:STATe
This command toggles the control lines of the user ports between INPut and OUTPut. With ON,
the user port is switched to INPut, with OFF to OUTPut.
Parameter
ON | OFF
Example
INP:UPOR:STAT ON
Characteristics
RST value: ON
SCPI: device–specific
Mode
all

Table of Contents

Related product manuals