EM500 Open-Loop Vector Control Inverter User Manual
111
stop bits)
4: 1-8-E-2 (1 start bit + 8 data bits + 1
even parity +2 stop bits)
5: 1-8-O-2 (1 start bit + 8 data bits + 1
odd parity +2 stop bits)
F10.03
Modbus Overtime
0.0 - 60.0, 0.0: Disabled (also works for
master - slave system)
s
0.0
F10.04
Modbus Response
Delay
1 - 20
ms
2
F10.05
Master-Slave
Communication
Function
0: Disabled
1: Enabled
0
F10.06
Master-Slave
Options
0: Slave
1: Master (Modbus protocol)
2: Master (CANSinee protocol)
0
F10.07
Data Sent by Master
0: Output Frequency
1: Set Frequency
2: Output Torque
3: Set Torque
4: PID Setting
5: Output Current
1
F10.08
Receiving
Proportionality
Factor of Slave
0.00 - 10.00 (Times)
1.00
F10.09
Sending Interval of
Master
0.000 - 30.000
s
0.200
F10.10
Communication
Protocol
0: Modbus-RTU Protocol
1: Profibus-DP Protocol
2: CANopen Protocol
3: DeviceNet Protocol
0
F10.11
Communication
Address of
Profibus-DP
Expansion Card
1 - 125
1
F10.12
Communication
Address of
CANopen
Expansion Card
1 - 127
1
F10.13
Communication
Address of
0 - 63
1