EM500 Open-Loop Vector Control Inverter User Manual
148
2: AI3
3: AI4
4: HDI
F28.11
Pressure Digital
given
0.00~Upper Limit Pressure value
MPa
0.80
F28.12
Early-warning
pressure
Pressure Digital given~ Warning
pressure
MPa
0.98
F28.13
Warning pressure
Early-warning pressure~ Maximum
pressure range
MPa
1.00
F28.14
Pressure
proportional gain
GP
0.00~100.00
5.00
F28.15
Pressure integral
time GTi
0.000~60.000, 0.000: No Integral
s
10.000
F28.16
Pressure differential
time GTd
0.000~60.000
ms
0.000
F28.17
Pressure integral
action range
0.00~100.00
%
100.00
F28.18
Pressure Regulation
Upper Limit
0.00~100.00
%
100.00
F28.19
Pressure regulation
Lower Limit
0.00~100.00
%
25.00
F28.20
lower Limit
pressure value
0.00~ Upper Limit pressure value
MPa
0.75
F28.21
Upper Limit
pressure value
lower Limit pressure value~
Maximum pressure range
MPa
0.85
F28.22
Pressure limit
deviation
0.00~100.00
%
0.00
F28.23
Pressure
disconnection
detection threshold
0.00~ Maximum pressure range
MPa
0.08
F28.24
Pressure
disconnection
detection Time
0.0~6000.0, 0.0 :The Function is
Disabled
s
0.0
F28.25
sensor selection
Ones Place:oil temperature sensor
0: General channel
1: Interface card
Tens Place: motor sensor
0: General channel
1: PT100