149
2: KTY84-130/150
3: PTC130/150
hundreds place: Air pressure sensor
0: General channel
1: Interface card
F28.26
Maximum
temperature range
60.0~160.0
125.0
F28.27
Temperature
feedback selection
0: AI1
1: AI2
2: AI3
3: AI4
4: HDI
1
F28.28
Temperature Digital
given
0.0~ Maximum temperature range
80.0
F28.29
Early-warning
Temperature
Temperature Digital given~ Warning
Temperature
105.0
F28.30
Warning
Temperature
Early-warning Temperature~ Maximum
temperature range
110.0
F28.31
Temperature
proportional gain
GP
0.00~100.00
5.00
F28.32
Temperature
integral time GTi
0.000~60.000, 0.000: No Integral
s
10.000
F28.33
Temperature
differential time
GTd
0.000~60.000
ms
0.000
F28.34
Temperature
integral action range
0.00~100.00
%
100.00
F28.35
Temperature
Regulation Upper
Limit
0.00~100.00
%
100.00
F28.36
Temperature
regulation
Lower Limit
0.00~100.00
%
100.00
F28.37
Fan stop
temperature
0.00~ Maximum temperature range
70.0
F28.38
Stopping
temperature running
time
10~7200
s
1200
F28.39
Fan start delay time
1~300
s
10