EasyManua.ls Logo

Sinee EM500 - Page 149

Sinee EM500
459 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EM500 Open-Loop Vector Control Inverter User Manual
149
2: KTY84-130/150
3: PTC130/150
hundreds place: Air pressure sensor
0: General channel
1: Interface card
F28.26
Maximum
temperature range
60.0~160.0
℃
125.0
〇
F28.27
Temperature
feedback selection
0: AI1
1: AI2
2: AI3
3: AI4
4: HDI
1
〇
F28.28
Temperature Digital
given
0.0~ Maximum temperature range
℃
80.0
●
F28.29
Early-warning
Temperature
Temperature Digital given~ Warning
Temperature
℃
105.0
●
F28.30
Warning
Temperature
Early-warning Temperature~ Maximum
temperature range
℃
110.0
●
F28.31
Temperature
proportional gain
GP
0.00~100.00
5.00
●
F28.32
Temperature
integral time GTi
0.000~60.000, 0.000: No Integral
s
10.000
●
F28.33
Temperature
differential time
GTd
0.000~60.000
ms
0.000
●
F28.34
Temperature
integral action range
0.00~100.00
%
100.00
●
F28.35
Temperature
Regulation Upper
Limit
0.00~100.00
%
100.00
●
F28.36
Temperature
regulation
Lower Limit
0.00~100.00
%
100.00
●
F28.37
Fan stop
temperature
0.00~ Maximum temperature range
℃
70.0
●
F28.38
Stopping
temperature running
time
10~7200
s
1200
●
F28.39
Fan start delay time
1~300
s
10
●

Table of Contents