EasyManua.ls Logo

Sinee EM500 - Page 183

Sinee EM500
459 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
EM500 Open-Loop Vector Control Inverter User Manual
183
17
Preset Torque
Terminal 1
With these two terminals, inverter can realize 4 torque
settings. See the table below (0/1: Present function terminal is
disabled / enabled) or table 7-19.
18
17
Preset Torque Setting
0
0
Determined by the torque setting source
(F13.01)
0
1
Preset Torque 1 (F13.03)
1
0
Preset Torque 2 (F13.04)
1
1
Preset Torque 3 (F13.05)
18
Preset Torque
Terminal 2
19
Acceleration/Decele
ration Time
Terminal 1
EM500 inverter has four groups of acceleration/deceleration
terminals, each group having two input terminals for
acceleration and deceleration. The setting of the combined
code of the 4 terminals, and relevant functions determines
present acceleration/deceleration time. As stated in the
following table: (0/1: Present function terminal
disabled/enabled). See function codes F15.03 - F15.13.
20
Acceleration/Decele
ration Time
Terminal 2
20
19
Acceleration/Deceleration Time
0
0
Group 1 (Acceleration Time: F00.14,
Deceleration Time: F00.15)
0
1
Group 2 (Acceleration Time: F15.03,
Deceleration Time: F15.04)
1
0
Group 3 (Acceleration Time: F15.05,
Deceleration Time: F15.06)
1
1
Group 4 (Acceleration Time: F15.07,
Deceleration Time: F15.08)
21
Acceleration/Decele
ration Prohibited
If the acceleration/deceleration time terminal is disabled, the
command for acceleration/deceleration is prohibited and
inverter’s output frequency remains the same. If inverter is
under the overcurrent protection status, run inverter as per
current limit mode.
22
Operation Pause
Inverter ramps to stop, but all running parameters are
memorized, for example PLC parameter and PID parameter. If
the terminal is disabled, inverter is reset to the pre-stop
running status.
23
External Fault Input
The fault signal of external devices can be inputted through
this terminal, so that inverter monitors and protects peripherals
at fault. Upon receiving external fault signal, inverter displays
“E14”, and coast to stop.
24
Switch Run
Together with F00.02, these two terminals determine the

Table of Contents

Related product manuals