EM500 Open-Loop Vector Control Inverter User Manual
418
Change the setting frequency (for example 50.00 Hz/1388 H) (F00.04=7)
Send: 01 41 70 15 13 88 3B 97
Return: 01 41 70 15 13 88 3B 97 (Normal)
Return: 01 C1 04 70 53 (When abnormal, assuming that slave fails)
1) Read the last fault information (read F19.00 - F19.05)
Send: 01 03 13 00 00 06 C1 4C