4-39
Group 06: Automatic Program Operation Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
06-00
Automatic
Operation Mode
Selection
0: Disable
0 - O O O X X X O
1: Execute a single cycle
operation mode.
Restart speed is based
on the previous
stopped speed.
2: Execute continuous
cycle operation mode.
Restart speed is based
on the previous
stopped speed.
3: After the completion of
a single cycle, the
on-going operation
speed is based on the
speed of the last stage.
Restart speed is based
on the previous
stopped speed.
4: Execute a single cycle
operation mode.
Restart speed will be
based on the speed of
stage 1.
5: Execute continuous
cycle operation mode.
Restart speed will be
based on the speed of
stage 1.
6: After the completion of
a single cycle, the
on-going operation
speed is based on the
speed of the last stage.
Restart speed is based
on the previous
stopped speed.
06-01
*Frequency Setting
of Operation-Stage
1
0.00~599.00 5.00 Hz O O O X X X O *1
06-02
*Frequency Setting
of Operation-Stage
2
0.00~599.00 10.00 Hz O O O X X X O *1
06-03
*Frequency Setting
of Operation-Stage
3
0.00~599.00 20.00 Hz O O O X X X O *1