4-218
08-23 Ground Fault (GF) selection
Range
0:
Disable
1: Enable
08-23=1:
If the inverter leakage current is greater than 50% of inverter rated current and the ground fault function is
enabled (08-23), the keypad will display a "GF Ground Fault" (GF), motor will coast to a stop and fault contact is
activated.
08-24
External Fault Operation Selection
Range
0:
Deceleration to stop
1: Coast to stop
2: Continue operation
Select operation selection when an external fault occurs. Refer to the multi-function inputs on how to set up the
inverter for an external fault input.
08-25
Detection selection of external fault
Range
0:
Immediately detect when the power is supplied
1: Start to detect during operation
08-25=0: When the inverter is supplied by power, detection external fault function will execute.
08-25=1: When the inverter is start to run, detection external fault function will execute.
08-30
Run Permissive Function Selection
Range
0:
Deceleration to Stop
1:
Coast to Stop
When 03-00~03-07=58,the inverter will stop by the set of 08-30
08-37
Fan Control Function
Range
0:
Start in operation
1: Permanent Start
2: Start in high temperature (except of the models of 2050, 4100 or the above)
08-38
Delay Time of Fan Off
Range
0~600 sec
08-37=0: The inverter start to run and the fan will follow to run. If the inverter stop and the time is longer than the
value of 08-38, the fan stop. If the temperature for heat sink is higher than the temperature of inside-detection and
the inverter doesn’t run, the fan will start run automatically.
08-37=1:
The inverter is supplied by power, the fan start to run.
08-37=2:
The temperature for heat sink is higher than the temperature of inside-detection, the fan start to run.
After The temperature for heat sink is lower than the temperature of inside-detection and the time is over 08-38,
the fan stop.