4-93 
 
00- 08  Communication frequency command – READ ONLY 
Range 
0.00~599.00 Hz 
 
Display the frequency reference when 00-05 or 00-06 is set to communication control (3). 
 
00-09 
Communication frequency command memory 
Range 
0: Don’t save when power supply is off. (00-08) 
1: Save when power is off. (00-08) 
Note: This parameter is only enabled in communication mode. 
00- 11 
Selection of PID Lower Limit Frequency
Range 
【0】:
PID is bound to lower limit frequency when inverter sleeps. 
【1】:
PID is bound to 0Hz when inverter sleeps. 
 
When inverter gets to sleep, 
 
00-11=0: PID is bound to lower limit frequency (00-13).   
 
00-11=1: PID is bound to 0 Hz.     
 
Note: Refer to descriptions of parameters 10-17~10-20 for details when inverter gets to sleep.     
 
00-12 
Upper Frequency Limit 
Range 
0.1~109.0 % 
 
Set the maximum frequency reference as a percentage of the maximum output frequency. Maximum output 
frequency depends on motor selection. 
Motor 1: Maximum frequency parameter 01-02. 
Motor 2: Maximum frequency parameter 01-16. 
 
00-13  Lower Frequency Limit 
Range  0.0~109.0 % 
 
Set the minimum frequency reference as a percentage of the maximum output frequency. Maximum output 
frequency depends on motor selection. Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 
Maximum frequency is set by parameter 01-16. 
 
Notes:  
-  When the frequency lower limit is set to a value greater than 0 and the inverter is started the output frequency 
will accelerate to the frequency lower limit with a minimum frequency defined by parameter 01-08 for motor 1 
and parameter 01-22 for motor 2. 
-  Frequency upper limit has to greater or equal to the frequency lower limit otherwise the inverter will display a 
SE01 (Set range error). 
-  Frequency upper and lower limit is active for all frequency reference modes.