■ 08-06 Motor Overload Operation Selection
08-06 Start-up mode of overload protection operation (OL1)
Range
0: Stop output after overload protection
1: Continuous operation after overload protection.
08-06=0: When the inverter detects a motor overload the inverter output is turned off and the OL1 fault
message will flash on the keypad. Press RESET button on the keypad or activate the reset function
through the multi-function inputs to reset the OL1 fault.
08-06=1: When the inverter detects a motor overload the inverter will continue running and the OL1 alarm
message will flash on the keypad until the motor current falls within the normal operating range.