4-88
S1
S2
S7
Forward/Reverse
selection
24VG
Operation
(normally open
Momentary switch)
Stop
(Normally closed
Momentary
switch)
Stop Command
(Off: Stop)
Run Command
(On:Run)
Figure 4.4.2 wiring example of 3-wire
.
Figure 4.4.3 3-wire operation
2-wire operation with hold function
To enable 2-wire operation with hold function set any of parameters 03-02 to 03-07 (terminal S3 ~ S8) to 53.
When this mode is enabled set terminal S1 (03-00=0) to forward and S2 (03-01=1) to reverse run command.