4-238 
 
11-02  Random PWM Function Selection 
Range 
0: 
Disable 
1: Enable 
 
11-02=0: Random PWM control disabled. 
 
11-02=1: Random PWM control enabled. Random PWM control can improve the ‘metal’ noise produced by the 
motor, more comfortable for the human ear. At the same time, Random PWM also limits RFI noise to a minimum 
level. The default setting of Random PWM control is disabled. Random PWM cannot be set if carrier frequency 
set in 11-01 is higher than 8 kHz. 
 
11-03  Automatic carrier lowering selection 
Range 
0: 
Disable 
1: Enable 
 
11-03=0: Automatic carrier frequency reduction during an overheat condition is disabled. 
 
11-03=1:
 Carrier frequency is automatically lowered in case the inverter heatsink overheated and will return to 
carrier frequency set in parameter 11-01 when the inverter temperature returns to normal. See section 3 for more 
information. 
 
11-04  S curve time setting at the start of acceleration 
11-05  S curve time setting at the end of acceleration 
11-06  S curve time setting at the start of deceleration   
11-07  S curve time setting at the end of deceleration 
Range 
0.00~2.50 Sec 
 
The S curve function for acceleration / deceleration is used to reduce mechanical impact caused by the load 
during momentary starting and stopping of the inverter. To use the S curve function set the time for acceleration 
start point (11-04), acceleration end point (11-05), deceleration start point (11-06) and deceleration end point 
(11-07). Refer to figure 4.4.85 for more information. 
 
 
Figure 4.4.85 S curve characteristic 
 
 
Total acceleration and deceleration time when the S curve is used: 
 
Accelerating time = Accelerating time 1 (or 2) + (11-04) + (11-05) 
                                               2 
 
Deceleration time = Deceleration time 1 (or 2) + (11-06) + (11-07) 
                                               2