4-183
Table 4.4.12 Selection of analog output terminals function (04-11 and 04-16)
04-11, 04-16
Parameter
setting
Function
(Keypad display)
Monitoring
Parameters
Group 12
Control Mode
VF VF+PG SLV SV
PM
SV
PM
SLV
SLV2
0 Output Freq 12-17
O O O O O O O
1 Freq Ref 12-16
O O O O O O O
2 Output Voltage 12-19
O O O O O O O
3 DC Voltage 12-20
O O O O O O O
4 Output Current 12-18
O O O O O O O
5 Output KW 12-21
O O O O O O O
6 Motor Speed 12-22
O O O O O O O
7 Output PF 12-23
O O O O O O O
8 AI1 Input 12-25
O O O O O O O
9 AI2 Input 12-26
O O O O O O O
10 Torque Ref 12-27
X X O O O O X
11 Current Iq 12-28
X X O O O O X
12 Current Id 12-29
X X O O O O X
13 Speed Deviation 12-30
X X X O O X X
14 Reserved
X X X X X X X
15 ASR Output 12-32
X O X O O X X
16 Reserved -
X X X X X X X
17 Voltage Ref Vq -
X X O O O O X
18 Voltage Ref Vd -
X X O O O O X
19 Reserved -
X X X X X X X
20 Reserved -
X X X X X X X
21 PID Input 12-36
O O O O O O O
22 PID Output 12-37
O O O O O O O
23 PID Setpoint 12-38
O O O O O O O
24 PID Feedback 12-39
O O O O O O O
25 Output Freq (SFS) -
O O O O O O O
26 PG Feedback 12-33
X O X O O X X
27 Reserved -
X X X X X X X
28 Comm Control -
O O O O O O O
04-19
AO2 Output Signal Type
Range
【0】: AO2 0~10V
【1】: AO2 4~20mA
It is required to be with the setting of SW6 on the conrtol board when AO2 analog output signal type is active.
When 04-19=0 (AO2 is 0~10V) and SW6 on the control board is V, AO2 output signal type is voltage.
When 04-19=1 (AO2 is 4~20mA and SW6 on the control board is I, AO2 output signal type is current.
04-20
Filter Time of AO Signal Scan
Range
【
0.00~0.50】Sec
Setting of parameter 04-20 is used for filtering momentary change in analog output signal. When it is enabled,
system response will lower down and interference protection will enhance.