4-33
Group 03: External Digital Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control mode
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2 Attribute
Selection Deceleration Time 2
03-44
Frequency
Detection Level 2
0.0~599.0 0.0 Hz O O O O O O O
03-45
Frequency
Detection Width 2
0.1~25.5 2.0 Hz O O O O O O O
03-46
Frequency
Detection Level 3
0.0~599.0 0.0 Hz O O O O O O O
03-47
Frequency
Detection Width 3
0.1~25.5 2.0 Hz O O O O O O O
* 2-wire operation mode: 29; 3-wire operation mode: 26.
* *If the maximum output frequency of motor is over 300HZ,the frequency resolution is changed to 0.1Hz
Group 04: External Analog Input and Output Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
04-00
AI Input Signal
Type
0: AI1:0~10V
AI2: 0~10V / 0~20mA
1 - O O O O O O O
1: AI1:0~10V
AI2: 4~20mA/ 2~10V
2: AI1: -10~10V
AI2: 0~10V/ 0~20mA
3: AI1: -10~10V
AI2: 4~20mA/ 2~10V
04-01
AI1 Signal
Scanning and
Filtering Time
0.00~2.00 0.03 s O O O O O O O
04-02
AI1 Gain
0.0~1000.0 100.0 % O O O O O O O *1
04-03
AI1 Bias
-100.0~100.0 0 % O O O O O O O *1
04-04 Reserved
04-05
AI2 Function
Setting
0: Auxiliary Frequency
0 -
O O O O
O O O
1: Frequency Reference
Gain
O O
O O O O O
2: Frequency Reference
Bias
O O
O O O O O
3: Output Voltage Bias
O O XX O
O O
4: Coefficient of
Acceleration and
Deceleration
Reduction
O O
O O O O O
5: DC Braking Current
O O O O
X X O
6: Over-Torque Detection
Level
O O
O O O O O
7: Stall Prevention Level
During Running
O O
XX X X O