4-209
08-Protection Parameters
08-00 Stall prevention function.
Range
xxx0b:
Stall prevention function is enabled during acceleration.
xxx1b: Stall prevention function is disabled during acceleration.
xx0xb: Stall prevention function is enabled during deceleration.
xx1xb: Stall prevention function is disabled during deceleration.
x0xxb: Stall prevention function is enabled during operation.
x1xxb: Stall prevention function is disabled during run.
0xxxb: Stall prevention function during run is based on the first acceleration time.
1xxxb: Stall prevention function during run is based on the second acceleration time.
08-01 Stall prevention level during acceleration
Range
20~200 %
08-02 Stall prevention level during deceleration
Range
200V: 330V~410V
400V: 660V~820V
575V:900~1000 V
690V:1080~1200 V
08-03 Stall prevention level during run
Range
30~200 %
08-21
Limit of stall prevention during acceleration
Range
1~100 %
08-22
Stall prevention detection time during run
Range
2~100 msec
08-40
Motor2 Acceleration Stall Prevention Level
Range
20~200 %
08-41
Motor2 Acceleration Stall Prevention Limit
Range
1~100 %
Stall prevention during acceleration (08-00=xxx0b)
Prevents the inverter from faulting (Overcurrent, Motor overload, Inverter overload) when accelerating with heavy
loads.
When the inverter output current reaches the level set in parameter 08-01 minus 15% the acceleration rate starts
to decrease. When the inverter output current reaches the level set in parameter 08-01 the motor stops
accelerating. Refer to figure 4.4.67 for more information.
Notes:
- Reduce stall prevention level during acceleration (08-01) in case the motor stalls (when the motor power is
smaller than the inverter rating.
- The inverter rated output current should be set to 100%.