3-41
3.18 Inverter Specifications
Basic Specifications 200V class
Inverter capacity (HP) 1 2 3 5 7.5 10 15 20 25
Out
ut rated
Heavy Duty type
H.D.
(150%/1min)
Rated output Capacity (KVA)
1.9 3 4.2 6.7 9.5 12.6 17.9 22.9 27.8
Rated output current (A)
5 8 11 17.5 25 33 47 60 73
Maximum applicable motor
*1
HP
(KW)
1
(0.75)
2
(1.5)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
Motor rated current (A)
*1
3.4 6.1 8.7 13.5 20.1 25.1 36.7 50.3 62.9
Normal Duty
type
N.D.
(120%/1min)
Rated output Capacity (KVA)
2.3 3.7 4.6 8.4 11.4 16.0 21.3 26.3 30.1
Rated output current (A)
6 9.6 12 22 30 42 56 69 80
Maximum applicable motor
*1
HP
(KW)
2
(1.5)
3
(2.2)
5
(3.7)
7.5
(5.5)
10
(7.5)
15
(11)
20
(15)
25
(18.5)
30
(22)
Motor rated current (A)
*1
6.1 8.7 13.5 20.1 25.1 36.7 50.3 62.9 72.9
The maximum output voltage (V)
3-phase, 200V ~ 240V
The maximum output frequency (Hz)
Based on parameter setting 0.1~599.0 Hz
Powe
Rated voltage, frequency
Single/3-phase
200V~240V, 50/60Hz
3-phase 200V~240V, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%
Inverter capacity (HP) 30 40 50 60 75 100 125 150
Out
ut rated
Heavy Duty type
H.D.
(150%/1min)
Rated output Capacity (KVA)
32.4 43.8 55.3 68.6 81.9 108 132 158
Rated output current (A)
85 115 145 180 215 283 346 415
Maximum applicable motor
*1
HP
(KW)
30
(22)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
Motor rated current (A)
*1
72.9 96.7 124 143.5 183.5 230 272 344
Normal Duty type
N.D.
(120%/1min)
Rated output Capacity (KVA)
41.9 52.6 64.4 76.2 95.3 118.9 152.4 172
Rated output current (A)
110 138 169 200 250 312 400 450
Maximum applicable motor
*1
HP
(KW)
40
(30)
50
(37)
60
(45)
75
(55)
100
(75)
125
(90)
150
(110)
175
(130)
Motor rated current (A)
*1
96.7 124 143.5 183.5 230 272 344 370
The maximum output voltage (V)
3-phase, 200V ~ 240V
The maximum output frequency (Hz)
Based on parameter setting 0.1~599.0 Hz
Powe
Rated voltage, frequency
Single/3-phase
200V~240V, 50/60Hz
3-phase 200V~240V, 50/60Hz
Allowable voltage fluctuation
-15% ~ +10%
Allowable frequency fluctuation
±5%