TECO A510s - Frequency Detection Operation

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-156
Table 4.4.9 Frequency detection operation
Function Detection operation of frequency confirmation Description
Frequency
agree
time
time
ONOFF
FWD
REV
03-14
03-14
Freq
Reference
Output
Frequency
Frequency
Agree
Signal
ON
Freq
Reference
Output is active when the output frequency
falls within the frequency reference minus
the frequency detection width (03-14).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 3 (Frequency
agree).
Set
frequency
agree
time
time
ONOFF
FWD
REV
03-14
Output
Frequency
Setting
Frequency
Agree
Signal
ON
03-13
03-13
03-14
Output is active the output frequency falls
within the frequency detection width (03-14)
of the set frequency detection level (03-13).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 3 (Set
frequency agree).
Output
frequency
detection 1
ON ONOFF OFF
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 1
Signal
Output is active when the output frequency
rises above the frequency detection level
(03-13) + frequency detection width (o3-14)
and deactivates when the output frequency
falls below frequency detection level (03-13).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 4 (Output
frequency detection 1).
Output
frequency
detection 2
OFF OFFON ON
03-14
03-14
03-13
03-13
03-13
03-13
time
time
Output
Frequency
Output
Frequency
Detection 2
Signal
ON
Output is active when the output frequency
is below the frequency detection level
(03-13) + frequency detection width (03-14)
and turns off when the output frequency falls
below frequency detection level.
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 5 (Output
frequency detection 2).
Output
frequency
detection
3
Output is active when the output frequency
rises above the frequency detection level
2(03-44) + frequency detection width
2(03-45) and deactivates when the output
frequency falls below frequency detection
level 2(03-44).
Any of the digital outputs function (03-11,
03-12 or 03-28) can be set to 50 (Output
frequency detection 3).