4-68
Group 17: Automatic Tuning Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F+
PG
SLV SV
PM
SV
PMS
LV
SLV2
17-00
Mode Selection of
Automatic Tuning*
0: Rotation Auto-tuning
VF:2
VF+PG
:2
SLV:6
SV:6
SLV2:6
- OO OO X X O
1: Static Auto-tuning
2: Stator Resistance
Measurement
3: Reserved
4: Loop Tuning
5: Rotation Auto-tuning
Combination (item:
4+2+0)
6: Static Auto-tuning
Combination (item:
4+2+1)
17-01
Motor Rated
Output Power
0.00~600.00
KVA KW O O O O X X O
17-02
Motor Rated
Current
0.1~1200.0
KVA A O O O O X X O
17-03
Motor Rated
Voltage
200V: 50.0~240.0 220
V O O O O X X O
400V: 100.0~480.0 440
575V:150.0~670.0 575
690V: 180.0~804.0 690
17-04
Motor Rated
Frequency
5.0~599.0 60.0 Hz O O O O X X O
17-05
Motor Rated
Speed
0~24000 KVA rpm O O O O X X O
17-06
Pole Number of
Motor
2~16 (Even) 4 Pole O O O O X X O
17-07
PG Pulse Number
0~60000 1024 ppr O O O O X X O
17-08
Motor no-load
Voltage
200V: 50~240
- V O O O O X X O
400V100~480
575V: 420~600
690V:504~720
17-09
Motor Excitation
Current
0.01~600.00 - A X X O O X X X
17-10
Automatic Tuning
Start
0: Disable
0 - OO OO X X O
1: Enable
17-11
Error History of
Automatic Tuning
0: No error
0 - OO OO X X O
1: Motor data error
2: Stator resistance
tunin
g
error
3: Leakage induction
tunin
g
error
4: Rotor resistance tuning
erro
r
5: Mutual induction tuning
erro
r
6: Encoder error
7: DT Erro
r

Table of Contents