4-171
04-External Analog Input / Output Parameter
04-00 AI input signal type
Range
0: AI1: 0~10V AI2: 0~10V/ 0~20mA
1: AI1: 0~10V AI2: 4~20mA/ 2~10V
2: AI1: -10~10V AI2: 0~10V/ 0~20mA
3: AI1: -10~10V AI2: 4~20mA/ 2~10V
04-01 AI1 signal scanning and filtering time
Range
0.00~2.00 Sec
04-02 AI1 gain
Range
0.0~1000.0%
04-03 AI1 bias
Range
-100~100.0%
04-05 AI2 function setting
Range
0: Auxiliary frequency
1: Frequency Reference Gain
2: Frequency Reference bias
3: Output Voltage Bias
4: Coefficient of acceleration and deceleration reduction
5: DC braking current
6: Over-torque Detection Level
7: Stall prevention Level During Running
8: Frequency lower limit
9: Jump frequency 4
10: Added to AI1
11: Positive torque limit
12: Negative torque limit
13: Regenerative Torque Limit
14: Positive / negative torque limit
15: Torque command/ Torque limit (in speed control)
16: Torque command/ Torque compensation
17: PTC Overheat Protection
04-06
AI2 signal scanning and filtering time
Range
0.00~2.00Sec
04-07 AI2 gain
Range
0.0~1000.0%
04-08 AI2 bias
Range
-100.0~1000.0%
Refer to the followings for 04-00 AI input signal type:
If AI1 is 0~10V, set parameter 04-00 to 0 or 1.
If AI1 is -10~10V, set parameter 04-00 to 2 or 3.