17-Automatic Tuning Parameters 
 
17-00  Mode selection of automatic tuning   
Range 
0: Rotational auto-tuning 
1: Static auto-tuning 
2: Stator resistance measurement   
3: Reserved 
4: Loop tuning 
5: Rotational Auto-tuning Combination (Item: 4+2+0) 
6: Static Auto-tuning Combination (Item: 4+2+1) 
 
17-01  Motor rated output power 
Range 
0.00~600.00 kW 
 
17-02 
Motor rated current 
Range 
For VF, VF+PG modes, 10%~200% of the inverter rated current   
For SLV, SV modes, 25%~200% of the inverter rated current. 
 
17-03 
Motor rated voltage 
Range 
200V:50.0~240.0 V 
400V:100.0~480.0 V 
575V:150.0~670.0 V 
690V: 180.0~804.0 V 
 
17-04 
Motor rated frequency 
Range 
5.0~599.0 Hz 
 
17-05 
Motor rated speed 
Range 
0~24000 rpm 
 
17-06 
Pole number of motor 
Range 
2~16 pole 
 
17-07 
Number of PG pulse 
Range 
0~60000 PPR 
 
17-08 
Motor no-load voltage 
Range 
50~240 V: 200V 
100~480 V: 400V 
575V: 420~600 V 
690V:504~720 V 
 
17-09 
Motor excitation current 
Range 
15~70% motor rated current 
 
17-10 
Automatic tuning start 
Range 
0: Disable 
1: Enable