4-102
00-31 Maximum frequency
Range
0: 400.00Hz
1:
1200.0Hz
00-31=0: Set maximum frequency to 400.00 Hz
00-31=1: Set maximum frequency to 1200.00 Hz
Note: Frequency reference on the keypad (00-05=0 / 00-06=0) is limited to the maximum frequency for motor 1
(01-02) or maximum frequency for motor 1 (01-31) setting. Actual maximum output frequency depends on duty
cycle selection (00-27) and control mode (00-00).
00-32 Application Selection **
Range
0: General
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC
5: Compressor
6: Hoist- * Consult TECO for the settings
7: Crane- * Consult TECO for the settings
Note: Before to set up 00-32 Application, it should do initialized setting (parameter 13-08) first. When setting
00-32, the I/O port function changed automatically. To avoid accident, be sure to confirm the I/O port signal of
inverter and external terminal control
,
00-32=1: Water supply pump
Parameter Name Value
00-00 Control mode selection 0: V/F
11-00 Direction lock selection 1: Forward direction only
01-00 V/F curve selection
6(60Hz)
4(50Hz)
07-00 Momentary stop and restart selection 1: Enable
08-00 Stall prevention function xx0xb: Stall prevention during deceleration