TECO A510s - Maximum Frequency; Application Selection; Water Supply Pump

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-102
00-31 Maximum frequency
Range
0: 400.00Hz
1:
1200.0Hz
00-31=0: Set maximum frequency to 400.00 Hz
00-31=1: Set maximum frequency to 1200.00 Hz
Note: Frequency reference on the keypad (00-05=0 / 00-06=0) is limited to the maximum frequency for motor 1
(01-02) or maximum frequency for motor 1 (01-31) setting. Actual maximum output frequency depends on duty
cycle selection (00-27) and control mode (00-00).
00-32 Application Selection **
Range
0: General
1: Water supply pump
2: Conveyor
3: Exhaust fan
4: HVAC
5: Compressor
6: Hoist- * Consult TECO for the settings
7: Crane- * Consult TECO for the settings
Note: Before to set up 00-32 Application, it should do initialized setting (parameter 13-08) first. When setting
00-32, the I/O port function changed automatically. To avoid accident, be sure to confirm the I/O port signal of
inverter and external terminal control
,
00-32=1: Water supply pump
Parameter Name Value
00-00 Control mode selection 0: V/F
11-00 Direction lock selection 1: Forward direction only
01-00 V/F curve selection
6(60Hz)
4(50Hz)
07-00 Momentary stop and restart selection 1: Enable
08-00 Stall prevention function xx0xb: Stall prevention during deceleration