4-62
Group 13: Maintenance Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
13-00
Inverter Capacity
Selection
---- - - O O O O O O O *4
13-01
Software Version
0.00-9.99 - - O O O O O O O *4
13-02
Clear Cumulative
Operation Hours
0: Disable to Clear
Cumulative Operation
Hours
0 - O O O O O O O *1
1: Clear Cumulative
Operation Hours
13-03
Cumulative
Operation Hours 1
0~23
- hr O O O O O O O *4
13-04
Cumulative
Operation Hours 2
0~65535
- day O O O O O O O *4
13-05
Selection of
Cumulative
Operation Time
0: Cumulative time in
power on
0 - O O O O O O O *1
1: Cumulative time in
operation
13-06
Parameters
Locked
0: Parameters are
read-only except 13-06.
2 - O O O O O O O *1
1 : User defined
parameters
2: All Parameters are
Writable
13-07
Parameter
Password
Function
0~9999
0 - O O O O O O O
13-08
Restore Factory
Setting
0 : No initialization
- - O O O O O O O
2 : 2 wire initialization
(60Hz)
(220/440V)
3 : 3 wire initialization
(60Hz)
(220/440V)
4 : 2 wire initialization
(50Hz)
(230/415V)
5 : 3 wire initialization
(50Hz)
(230/415V)
6 : 2 wire initialization
(50Hz)
(200/380V)
7 : 3 wire initialization
(50HZ)
(200/380V)
8 : PLC initialization
9: 2 wire Initialization
(60Hz)
(230/460V)
10: 3 wire Initialization
(60Hz)