03-0X =32: Sync command
Selects between frequency reference source from pulse input or frequency reference source selected by
parameter 00-05. Refer to page 4-116 for more information.
Input Ref. Source Frequency Reference / Run/Stop Command Source
ON Pulse Input
- Frequency reference set by pulse input
OFF Parameter 00-05
- Frequency reference source selected by parameter 00-05
Note:
- Function is disabled when the Local/Remote selection (25) or Remote mode selection (26) is active.
- To switch between local and remote the inverter has to be stopped.
03-0X =33: DC braking
When input is active DC-Injection braking is enabled during start and stopping of the inverter.
DC Injection braking is disabled when a run or jog command is active. Refer to the DC braking time diagram in
Figure 4.4.24.
Figure 4.4.24 DC braking timing diagram
03-0X =35: Timing function
Refer to the "time function" parameter 03-37 and 03-38.
03-0X =36: PID Soft start disable
Refer to the "PID Control" function of PID function parameter group 10.
03-0X =37: Traverse operation
03-0X =38: Upper Deviation of traverse operation
03-0X =39: Lower Deviation of traverse operation
See “Wobble Frequency” function in parameter group 19
03-0X =40: Switching between motor 1 and motor 2