EasyManua.ls Logo

TECO A510s - Basic Parameters

TECO A510s
519 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
4-19
Group 00: Basic Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F
+PG
SLV SV
PM
SV
PM
SLV
SLV2
00-00
Control Mode
Selection
0: V/F
0 - O O O O O O O *3
1: V/F+PG
2: SLV
3: SV
4: PMSV
5: PMSLV
6: SLV2
00-01
Motor’s Rotation
Direction
0: Forward
0 - O O O O O O O *1
1: Reverse
00-02
Main Run
Command Source
Selection
0: Keypad
1 - O O O O O O O
1: External Terminal
(Control Circuit)
2: Communication
Control (RS-485)
3: PLC
00-03
Alternative Run
Command
Selection
0: Keypad
2 - O O O O O O O
1: External Terminal
(Control Circuit)
2: Communication
Control (RS-485)
3: PLC
00-04 Language
0: English
0 - O O O O O O O
1: Simplified Chinese
2: Traditional Chinese
3: Turkish
00-05
Main Frequency
Command Source
Selection
0: Keypad
1 - O O O O O O O
1: External Terminal
(Analog 1)
2: Terminal Command
UP/DOWN
3: Communication
Control (RS-485)
4: Pulse Input
5: Reserved
6: Reserved
7: AI2 Auxiliary
Frequency
00-06
Alternative
Frequency Source
Selection
0: Keypad
3 - O O O O O O O
1: External Terminal
(Analog 1)
2: Terminal Command
UP/DOWN
3: Communication
Control (RS-485)
4: Pulse Input

Table of Contents