8-6
8.5 Emergency Stop
The emergency stop time is used in combination with multi-function digital input function #14
(Emergency stop). When emergency stop input is activated the inverter will decelerate to a stop using
the Emergency stop time (00-26) and display the [EM STOP] condition on the keypad.
Note: To cancel the emergency stop condition the run command has to be removed and emergency stop input
deactivated.
Example: Emergency Stop Switch with NPN wiring set for input terminal S5 (03-04 = 14).
00-26 Emergency stop time
Range
0.1~6000.0 Sec