4-357
(2) SW2 (Termination Resistance)
SW2 Description
ON
Used in terminal resistance between B+
and A-.
OFF
Not used in terminal resistance between
B+ and A-.
4.7.6 Parameter setting
PLC can monitor the inverter A510S via Profibus DP communication card by the setting of the
following parameters. When parameter 09-01 is set to 4: Profibus, PLC can monitor the inverter
A510, but cannot perform the operation command and frequency command. It is required to set
parameter 00-02 to 2: communication control, to perform the operation command. Set parameter
00-05 to 3: communication control, to perform the frequency command.
Code Parameter Name Setting Range Default
09-01
Communication Mode
Selection
4: Profibus
0
00-02
Main Run Command Source
Selection
2:Communication
Control
1
00-05
Main Frequency Command
Source Selection
3: Communication
Control
1
4.7.7 Profibus I/O List
When Hardware Configuration in PLC program defines I/O address of Profibus DP communication
card as 400-431, its corresponding Profibus address and parameters are as follows:
Data Input (Read inverter’s data from PLC)
No..
Profibus
address
Bit Contents
1 PIW400
Status Signal
0 Operation Status 1 : Run 0 : Stop
1 Direction Status 1 : Reverse 0 : Forward
2 Operation Ready Status 1 : Ready 0 : Unready
3 Error 1 : Abnormal
4 Alarm 1 :“ON”
5 Zero Speed 1 :“ON”
6 440 Model 1 :“ON”
7 Frequency Agree 1 :“ON”
8 Setting Frequency Agree 1 :“ON”
9 Frequency Detection 1 1 :“ON”
A Frequency Detection 2 1 :“ON”
B Low Voltage 1 :“ON”
C Inverter no output 1 :“ON”
D Frequency not based on communication 1 :“ON”
E SeqNotFromComm 1 :“ON”
F Over-torque 1 :“ON”