4-164
Figure 4.4.28 PID control
03-35 Function setting of pulse output
Range
1: Frequency command
2: Output frequency
3: Output frequency after the soft start
4: Motor speed
5: PID feedback
6: PID input
7: PG output (with PG card)
Refer to Table 4.4.10 for pulse output function selection overview.
03-36
Scale of pulse output
Range
0~32000 Hz
Pulse output scaling, 100% = Maximum pulse frequency (see table 4.4.10).
Note: When setting 03-35 to 2 (output frequency) and setting 03-36 to 0 (0 Hz), PO's pulse output and the
inverter output frequency are sync.
Table 4.4.10 Pulse output function selection
03-35 Function Screen display (LCD) Parameter 100%
1 Frequency command Freq Ref 12-16 01-02
2 Output frequency (Fout) Output Freq 12-17 01-02
3 Output frequency after soft-start Output Freq (SFS) - 01-02
4 Motor speed (rpm) Motor Speed 12-22 01-02
5 PID feedback PID Feedback 12-39 01-02
6 PID input PID Input 12-36 01-02
7 PG output PG Pulse Output
Note: Selection 1~4 are related to the motor speed, 5 and 6 are related to PID and 7 is related to PG.
Setup the pulse output
Use 03-36 (pulse output scale) to set the pulse output frequency to100% signal value of the selected item.
Please refer to the figure 4.4.29.