4-66
Group 16: LCD Function Parameters
Code Parameter Name Setting Range Default Unit
Control mode
Attribute
V/F
V/F+
PG
SLV SV
PM
SV
PMS
LV
SLV2
16-00
Main Screen
Monitoring
5~79
when using LCD to
operate, the monitored
item displays in the first
line. (default is frequency
command)
16 - O O O O O O O *1
16-01
Sub-Screen
Monitoring 1
5~79
when using LCD to
operate, the monitored
item displays in the
second line. (default is
output frequency)
17 - O O O O O O O *1
16-02
Sub-Screen
Monitoring 2
5~79
when using LCD to
operate, the monitored
item displays in the third
line. (default is output
current)
18 - O O O O O O O *1
16-03 Display Unit
0~39999
Determine the display
way and unit of frequency
command
0 - O O O O O O O
0: Frequency display unit
is 0.01Hz
1: Frequency display unit
is 0.01%
2: Frequency display unit
is rpm.
3~39: Reserved
40~9999:
Users specify the format,
Input 0XXXX represents
the display of XXXX at
100%.
10001~19999:
Users specify the format;
Input 1XXXX represents
the display of XXX.X at
100%.
20001~29999:
Users specify the format,
Input 2XXXX represents
the display of XX.XX at
100%.
30001~39999:
Users specify the format,
Input 3XXXX represents
the display of X.XXX at
100%.
16-04 Engineering Unit
0: without using
engineering unit
0 - O O O O O O O
1: FPM