4-293
20-28=0: Forward operation, phase A is leading (phase B is leading for reversal operation).
20-28=1: Forward operation, phase B is leading (phase A is leading for reversal operation).
Figure 4.4.118 PG and motor rotation direction
Motor direction is determined as below:
Forward: The motor direction is counter-clockwise when inverter runs in forward direction (see figure 4.4.119.)
Figure 4.4.119 Motor operation direction
Forward: The motor direction is clockwise when inverter runs in forward direction (see figure 4.4.120.)
Refer to the below figure 4.4.120 for PG feedback pulses.
Figure 4.4.120 PG operation direction
(6) PG pulse dividing ratio (20-29)
Sets the pulse divider ratio between the PG input and PG output.
The left most digit (3
rd
) represent the numerator and the last to represent the denominator.
Ratio is calculated as follows:
20-29= □□, = n kk
Range n: 0 to 1
Range k: 1 to 32
Ratio = (1+n)/k