4-191
Example 3: Automatic operation mode – Single cycle and continue running at last speed of the cycle
In this example the inverter executes a single cycle and continue running at last speed of the cycle.
Parameter Settings:
06-00= 3 or 6 (Single cycle operation)
06-32~06-35= 1 (Forward)
06-36~06-47= 0
Other parameter = Enter same setting as that of Example 1.
Freq.
50 Hz
30 Hz
15 Hz
20 Hz
20s 25s 30s 40s
05-01
06-01
06-02
06-15
06-16 06-17 06-18
06-31
Figure 4.4.54 Single cycle automatic operation (continuous)
06-00= 1 to 3:
After a stop the inverter will restart with the incomplete step when the run command is re-applied.
06-00= 4 to 6:
After a stop the inverter will restart with the first step of the cycle when the run command is re-applied.
Notes:
- Acceleration/ deceleration time is set with the setting of 00-14 and 00-15 in the automatic operation mode.
- If the setting value of parameters 06-16~06-31 is 0, automatic operation mode is not active.