4-223
09-06: RS-485 communication error detection time
09-07: Stop selection of RS-485 communication failure
= 1: Deceleration to stop by deceleration time 00-15
= 2: Coast to stop
= 2: Deceleration to stop using the deceleration time of 00-26 (emergency stop time)
= 3: Continue to operate (only shows a warning message, press the stop button to stop operation)
09-08: Comm. fault tolerance count
When the number of communication errors exceeds the value set in parameter 09-08 the inverter will display the
comm. Fault alarm.
09-09: Wait time of inverter transmission (09-09).
Sets the inverter response delay time. This is the time between the controller message and the start of the
inverter response message. Refer to figure 4.4.76. Set the controller receive time-out to a greater value than the
wait time parameter (09-09).
Figure 4.4.76 Communication Message Timing