4-196
07- 04
Direct Start at Power on
Range
0】:
When the external run command is enabled, direct start at power up
1】:
When the external run command is enabled, unable to direct start at power-up.
07-04=0,
If operation switch is conducted at power up, the inverter will start automatically.
07-04=1,
If operation switch is not conducted at power up, the inverter is not able to start and the warning signal of STP1
flashes. It is required to turn off the operation switch first, and then make it be conducted to start the inverter.
07- 05
Delay of Direct Start at Power on
Range
1.0~300.0 Sec
If 07-04=0, it will count the delay time set by 07-05 first when the inverter starts directly at power on. When the
delay time is completed, it starts to run.
DANGER
When 07- 04=0 and the external run is set (00-02/ 00-03=1),
If the operation switch is conducted at power up,
the inverter starts automatically. It is suggested to turn off
the power switch and operation switch at power failure to avoid the damage to the user or the machine when
the inverter reconnects.
Wen 07- 04=1 and the external run is set (00-02/ 00-03=1),
If the operation switch is not conducted at power up, the inverter is not able to start and the warning signal
ofSTP1 falshes. It is required to turn off the operation switch first and the delay time of direct start at power
up is completed. Then make it be conducted to start th inverter.
07-06 DC injection braking starting frequency
Range
0.0~10.0 Hz
DC injection braking start frequency is the level the output frequency has to reach before DC braking injection
function is activated.
07-07 DC injection braking current
Range
0~100 %
DC Injection braking current as percentage of the inverter rated current. Increasing this level will increase the
amount of heat generated by the motor windings. Do not set this parameter higher than the level necessary to
hold the motor shaft.
07-08 DC injection braking time at stop
Range
0.00~10.00 Sec
Duration of DC injection braking during a stop operation. DC injection braking at stop is disabled when parameter
07-08 is set to 0 sec.
07-16 DC injection braking time at start
Range
0.00~10.00 Sec