4-259
13-06 Parameters lock
Range
0:
Parameters are read-only except 13-06
1: User Defined Parameters
2: All parameters are writable
13-07 Parameter password function
Range
0~9999
13-08 Restore factory setting / Initialize
Range
0:
No Initialization
1: Reserved
2: 2-wire initialization (220/440V) [60Hz]
3: 3-wire initialization (220/440V) [60Hz]
4: 2-wire initialization (200/415V) [60Hz]
5: 3-wire initialization (200/415V) [60Hz]
6: 2-wire initialization (200/380V) [60Hz]
7: 3-wire initialization (200/380V) [60Hz]
8: PLC initialization
Other: Reserved
Use parameter 13-08 to initialize the inverter to factory default. It is recommended to write down the modified
parameters before initializing the inverter. After initialization, the value of 13-08 will return to zero automatically.
13-08=2: 2-wire initialization (220V/440V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Figure 4.4.1.
Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class)
13-08=3: 3-wire initialization (220V/440V)
Multi-function digital input terminal S7 controls the forward / reverse direction, and terminals S1 and S2 are set for
3-wire start operation and stop command.
Refer to Figure 4.4.2 and Figure 4.4.3 for 3-wire type operation mode.
Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class)
13-08=4: 2-wire initialization (230V/415V)
Multi-function digital input terminal S1 controls forward operation / stop command, and S2 controls reverse
operation / stop command. Refer to Figure 4.4.1.
Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class)
13-08=5: 3-wire initialization (230V/415V)
Multi-function digital input terminal S5 controls the forward / reverse direction, and terminals S1 and S2 are set for
3-wire start operation and stop command.
Inverter input voltage (01-14) is automatically set to 220V (200V class) or 440V (400V class)