4-117 
Table 4.4.5 40HP and above V/F curve selection 
 
Type  Specification  01-00  V/F curve
*1
  Type Specification 01-00  V/F curve
*1
 
General application 
50Hz 0 
 
(Hz)
200
50
0
1.3
(V)
(0)
8.9
2.5
15.6
High Staring Torque
‡
 
50Hz
Low 
Starting 
Torque
8 
 
(Hz)
0
(V)
(9)
501.3
2.5
(8)
200
16.7
16.0
9.4
8.9
High 
Starting 
Torque
9 
60Hz 
60Hz 
Saturation 
1 
 
(Hz)
200
60
0
1.5
(V)
(2)
(1),(F)
50
8.9
3
15.6
60Hz
Low 
Starting 
Torque
A 
 
(Hz)
200
0
(V)
(B)
601.5
3
(A)
16.7
16.0
9.4
8.9
F 
(Def.
Val.)
50Hz 
Saturation 
2 
High 
Starting 
Torque
B 
Descending torque (Mechanics of wind, water and other force) 
72Hz 3 
(Hz)
72
0
(V)
(3)
601.5
3
8.9
15.6
200
Constant-power torque (Reducer) 
90Hz C 
(Hz)
200
90
(V)
(C)
600
1.5
8.9
3
15.6
50Hz 
Variable 
Torque 1 
4 
 
(Hz)
0
(V)
(5)
501.3 25
(4)
200
8.9
60.1
41.8
 
120Hz D 
 
(Hz)
200
1200
(V)
(D)
601.5
8.9
3
15.6
 
Variable 
Torque 2 
5 
60Hz 
Variable 
Torque 3 
6 
 
(Hz)
0
(V)
(7)
601.5 30
(6)
200
8.9
60.1
41.8
180Hz E 
 
(Hz)
200
1800
(V)
(E)
601.5
8.9
3
15.6
Variable 
Torque 4 
7 
 
*1. Values shown are for 200V class inverters; double values for 400V class inverters. 
*2. High-speed motor (operation frequency > 400Hz) is not supported above 40HP. 
 
‡
Select high starting torque only for the following conditions. 
(1)  The power cable length is > 150m (492ft). 
(2)  Voltage drop at startup is high. 
(3)  An AC reactor is used on the input side or output side of the inverter. 
(4)  Motor power lower than the inverter rated power.