4-215
08-09 Selection of input phase loss protection
Range
0:
Disable
1: Enable
08-09=0: Input phase loss detection is disabled.
08-09=1:
Input phase loss detection is enabled. Keypad shows "IPL input Phase Loss" (IPL), when an input
phase loss is detected the inverter output is turned off and the fault contact is activated.
Note: The input phase loss detection is disabled when the output current is less than 30% of the inverter rated
current.
08-10 Selection of output phase loss protection
Range
0:
Disable
1: Enable
08-10=0: Output phase loss detection is disabled.
08-10=1:
Output phase loss detection is enabled. Keypad shows "OPL Output Phase Loss" (OPL), when an
output phase loss is detected and the inverter output is turned off and the fault contact is activated.
Note: The output phase loss detection is disabled when the output current is less than 10% of the inverter rated
current.
08-13 Selection of over-torque detection
Range
0:
Over-torque detection is disabled
1: Start to detect when reaching the set frequency
2: Start to detect when the operation is begun
08-14 Selection of over-torque action
Range
0:
Deceleration to stop when over-torque is detected.
1: Displays warning when over-torque is detected. Continue operation.
2: Coast to stop when over-torque is detected
08-15 Level of over-torque detection
Range
0~300 %
08-16 Time of over-torque detection
Range
0.0~10.0 Sec
08-17 Selection of low-torque detection
Range
0:
Low-torque detection is disabled
1: Start to detect when reaching the set frequency
2: Start to detect when the operation is begun
08-18 Selection of low-torque action
Range
0:
Deceleration to stop when low-torque is detected
1: Display warning when low-torque is detected. Go on operation
2: Coast to stop when under-torque is detected