4-97
B. Switch of Acceleration/Deceleration time according to motors
03-00~03-07 set to 40 (Switching between motor 1/motor 2),it can switch motors by digital input. This
function I only for V/F control mode and V/F +PG card mode.
Chose for motor1, acceleration and deceleration time of multi-speed depends on
Figure 4.4.1.
Chose for motor, acceleration and deceleration time of multi-speed depends on
the following Figure.
Chose moto
r
2
acceleration and
deceleration time 1
(
Set 03-00 to 03-07 = 10
)
acceleration deceleration
0 Taccc3
(
00-21
)
Tdec3
(
00-22
)
1 Taccc4
(
00-23
)
Tdec4
(
00-24
)
C. Automatically switch acceleration/deceleration time
When output frequency equals to the value of 00-25, it follows the value of 00-25 to automatically switch
acceleration/deceleration time1 and time2.Please refer to the following Figure
4.4.8.
Figure 4.4.8 automatically switch Acceleration/Deceleration time
When output frequency Fout 00-25 : Acceleration/deceleration time = Acceleration time1/
deceleration time 1(00-14 and 00-15).
When output frequency Fout 00-25 : Acceleration/deceleration time = Acceleration time4/
deceleration time 4(00-23 and 00-24)
When 03-00~03-07 set to 10 (Acceleration/ Deceleration Time Selection 1) and 03-00~03-07 set to 3
(Acceleration/ Deceleration Time Selection 2), the priority is higher than 00-25.
00-18 Jog frequency
Range
0.00~599.00 Hz
00-19 Jog acceleration time
Range
0.1~6000.0 Sec
00-20 Jog deceleration time
Range 0.1~6000.0 Sec
Jog acceleration time (00-19) is the time required to accelerate from 0 to 100% of maximum output frequency.
Jog deceleration time (00-20) is the time required to decelerate from 100 to 0% of maximum output frequency.
Motor 1: Maximum frequency is set by parameter 01-02 and Motor 2 Maximum frequency is set by parameter
01-16.