4.7 Profibus Communication Protocol
4.7.1 Descriptions
This section describes details for the option card of JN5-CM-PBUS Profibus DP communication
protocol (JN5-CM-PBUS) and the inverter’s communication modes coupled with the Profibus DP
communication card and PLC.
4.7.2 Specifications
Note: When Profibus DP communication card is used, inverter’s RS-485 communication port
cannot be used. If Profibus DP communication card and RS-485 is used simultaneously, the error
will occur.
Specifications Contents
Main Functions Providing A510S Profibus-DP communication function
Inverter Models F510 / A510S series
Installation
Installing in the slot of option card on the inverter’s control board
Communication Card’s
Maximum Connection
Numbers
32 DP-Slave node
Transmission Speed of
Auto-switch (bit/Sec)
9.6K 19.2K 93.75K 187.5K 500K 1.5M 3M 6M 12M
Transmission Distance (m) 1200 1200 1200 1000 400 200 100 100 100
Connection Medium
Profibus Layer2 Cable
Optocouplers Pressure
Common Mode Rejection Vcm=50V,dV/dt=5000V/uSec
Access to Inverter’s
Parameters
Read 16 Words, Write in 16 Words
Termination Resistors Built-in Communication card (DIP Switch setting)
LED Indicator Operation display, Profibus communication function
Dimensions
101 mm x 40.5 mm