Data Output (Write data into the inverter from PLC)
No.
Profibus
address
Bit Content
1 PQW400
Operation Signal
0 Operation Command 1 : Run 0 : Stop
1
Reverse Command 1 : Reverse rotation 0 : Forward rotation
(Limit Fwd./ Rev. rotation by the setting of parameter 11-00
0: Allow FWD/REV 1: Allow FWD only 2: Allow REV only )
2 External Error 1 : Error
3 Error Reset 1 : Reset
4 Reserved
5 Reserved
6 Multi-function terminal S1 1 :“ON”
7 Multi-function terminal S2 1 :“ON”
8 Multi-function terminal S3 1 :“ON”
9 Multi-function terminal S4 1 :“ON”
A Multi-function terminal S5 1 :“ON”
B Multi-function terminal S6 1 :“ON”
C Reserved
D Reserved
E Controller Mode 1 : “ON”
F Reserved
No.
Profibus
address
Bit Content
2 PQW402 Frequency Command (6000/60Hz)
3 PQW404 Torque Command (+/-8192 corresponding to rated torque +/-100%)
4 PQW406 Speed limit (+/- 120 corresponding +/-120%)
5 PQW408 AO1 (0.00V ~ 10.00V)
6 PQW410
AO2 (0 ~ 1000) Voltage (corresponding to 0.00~10.00V) Current
(corresponding to 4mA~20mA)
7 PQW412
DO Status
0
R1A-R1C Status (0: Non-action 1: Action)
(only enabled in 03-11=32)
1
R2A-R2C Status(0: Non-action 1: Action)
(only enabled in 03-12=32)
2
R3A-R3C Status( 0: Non-action 1: Action)
(only enabled in 03-39=32)
3-15 Reserved
8 PQW414
Reserved
9 PQW416
10 PQW418
11 PQW420
12 PQW422
13 PQW424
14 PQW426
15 PQW428
16 PQW430